Installing an automatic water pump controller involves confirming compatibility, preparing the mounting location, connecting the supply, motor and supported sensors according to the model diagram, and commissioning the intended operating sequence. Electrical work must be carried out by qualified personnel; a generic article cannot replace the equipment's instructions.

Updated 19 October 2026

This checklist helps the owner and installer agree what must be ready and what should be verified before handover. For choosing the equipment itself, use the controller selection guide.

Before installation begins

  • Identify the exact controller model and obtain its installation and operating documentation.
  • Record the motor's voltage, phase, frequency, rated current and power.
  • Confirm any required external motor-starting components.
  • Write the intended start condition, stop condition and interlocks.
  • Confirm supported sensors and the specified installation environment.

Do not infer compatibility from enclosure size, wire colours or the advertised power alone. A replacement can require different inputs or terminal arrangements even when it performs a similar job.

1. Prepare the location and mounting

Use the mounting orientation, clearances and environmental limits stated for the model. Allow safe access for operation and service. Consider water leaks, flooding, condensation, direct exposure, heat and damage to cables. An enclosure description does not permit every form of outdoor exposure.

For an in-line electronic pressure/flow device, its permitted pipe orientation and hydraulic position also need to be checked. A wall-mounted motor panel and an in-line controller do not share one mounting procedure.

2. Follow the actual electrical diagram

The installer should confirm isolation, protective earthing, the required protection and the supply/motor circuit before making connections. Cable sizing, protective devices and connection details must be determined for the equipment and installation. Front-panel OFF is not proof that the supply is isolated.

Use the connection-document checklist to distinguish a model-specific diagram from an illustrative example. Never connect by copying terminal numbers from a different panel. Internal capacitors may retain energy after disconnection.

3. Identify each sensor's job

Label the receiving-vessel demand, the normal stop signal and any separate source-water interlock. Filling and drainage use different logic. Confirm whether an input expects a contact, electrode arrangement or another signal type, as defined by the manual.

Do not apply supply voltage to an unknown input or bridge a protection terminal to obtain a start. The required response to a missing or failed signal should be agreed for the application and supported by the selected equipment.

4. Commission the complete sequence

Checks to agree and record before handover
CheckExpected evidence
Initial configurationModel, operating mode and settings documented against the intended duty.
Demand responseThe configured demand condition requests pumping as intended.
Normal stopThe required stop condition ends operation.
Interlocks and protectionsRelevant functions verified using the approved commissioning method.
Water deliveryThe pump and water system perform the agreed duty.
Recovery behaviourFault acknowledgement and post-interruption behaviour understood and recorded.

Do not create an unsafe condition merely to demonstrate an alarm. A single successful start is not a full commissioning check. Verify the normal stop and relevant inhibits as well as the motor running.

5. Hand over the information needed for service

Retain the model manuals, applicable circuit diagram, motor details, sensor labels, settings and commissioning results. Explain normal standby indications, the operator's permitted actions and when professional service is required.

Record visible fault indications before resetting. Repeated trips, unusual cycling or failure to reach the normal stop condition require investigation. The fault-record guide provides a practical service handover format.

Where to find the right instructions

Use the Winning Controller manual download page and confirm the document matches the installed model and configuration. Keep the installation record with the equipment so future maintenance does not depend on an unverified generic diagram.